P26 thru P30: ERROR memory
G
These parameters hold the error memory information. All errors are saved and shown in
these parameters.
P26 1ST ERROR
XX Error
Actual Value Output Freq.
Left fct. Up fct. Down fct. Right fct.
The errors include the following information:
XX = error code / Error = description
Date and time of when the error occurred
P35 KWH COUNTER
G
This parameter registers the power consumption of the motor as a mean value over 1
hour.
P35 KWH COUNTER
XXXXX kWh
Actual Value Output Freq.
Left fct. Up fct. Down fct. Right fct.
For information about how to reset the counter, see parameter 1140 CLR.KWH CNT.
8.3.3 M40 DIAGNOSTICS
MENU SCOPE
This submenu includes the following software parameters:
Production date
Actual temperature
Actual output current
Actual input voltage
Actual output frequency
Software version of the Power Board
During operation, the information in these parameters is read-only. No changes are
permitted.
P41 PROD.DATE
Shows the production date of the control board; the display format is YYYYWW (year,
week).
P41 PROD.DATE
20YYWW
Actual Value Output Freq.
Left fct. Up fct. Down fct. Right fct.
8 Programming
52 HVL 2.015-4.220 Installation, Operation, and Maintenance Manual

Table of Contents

Other manuals for Xylem hydrovar

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Xylem hydrovar and is the answer not in the manual?

Xylem hydrovar Specifications

General IconGeneral
Frequency50/60 Hz
Control typeVariable speed drive
Protection classIP55
Communication protocolsModbus
Relative Humidity5% - 95% (non-condensing)
AltitudeUp to 1000 m without derating
Input voltage200-690 V AC
Storage Temperature-25°C to +70°C (-13°F to 158°F)