EasyManua.ls Logo

Xylem hydrovar - Page 84

Xylem hydrovar
116 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Setting Description Connected to terminals (Premium
Card)
Off Required value 2 not used. -
Digital
Digital
The internal required value 2 is used.
For setting, see P02REQUIRED VAL. or
P825 REQ.VAL.2
-
Analog U 0-10V The required value 2 is set by the
value of voltage signal.
X3/11-12
Analog I 0-20mA The required value 2 is set by the
value of current signal.
X3/10-11
Analog I 4-20mA The required value 2 is set by the
value of current signal.
X3/10-11
P815 SW.REQ.VAL.
P815 SW.REQ.VAL.
Setpoint 1
Actual Value Output Freq.
Left fct. Up fct. Down fct. Right fct.
Configure the switching between required value 1 and 2. Possible setting are:
Setting Switching possibilities Action
Setpoint 1 No Only required value 1 is active
Setpoint 2 No Only required value 2 is active
Switch Dig 1 Manual Close digital input 1 (X1/14-15)
Switch Dig 2 Manual Close digital input 2 (X3/1-2) on
Premium Card
P820 REQ.VAL.1
P820 REQ.VAL.1
XX.X bar
Actual Value Output Freq.
Left fct. Up fct. Down fct. Right fct.
Sets the digital required value 1 in bar (possible setting 0.0 - P420 SENSOR RANGE).
The value is active in all operation mode (but not Actuator mode), if the following applies:
P805 C.REQ.VAL.1 is set to Digital.
P815 SW.REQ.VAL. is set to Setpoint 1 or the REQUIRED VALUE 1 is selected via digital
input (open).
If the current required value is active, P02 REQUIRED VAL. can override the pre-selected
required value.
8 Programming
82 HVL 2.015-4.220 Installation, Operation, and Maintenance Manual

Table of Contents

Other manuals for Xylem hydrovar

Related product manuals