1.21 Defaults by Drive Model and Duty Rating ND/HD
134 YASKAWA TOEPYAIGA5002A GA500 DRIVE PROGRAMMING
No.
*1
Name Unit Default
- Drive Model - 2001 2002 2004 2006
C6-01
Normal /
Heavy Duty
Selection
-
HD ND HD ND HD ND HD ND
0 1 0 1 0 1 0 1
o2-04
Drive Model
(KVA)
Selection
Hex. 60 61 62 63
E2-11
(E4-11, E5-
02)
Motor Rated
Power
kW 0.1 0.2 0.2 0.4 0.4 0.75 0.75 1.1
L3-06
Stall Prevent
Level during
Run
% 150 120 150 120 150 120 150 120
L3-24
Motor Accel
Time @ Rated
Torque
s 0.178 0.178 0.178 0.178 0.178 0.142 0.142 0.142
L8-02
Overheat
Alarm Level
°C 115 115 115 115 115 115 120 120
L8-09
Output Ground
Fault
Detection
- 0 0 0 0 0 0 0 0
n1-03
Hunting
Prevention
Time Constant
ms 10 10 10 10 10 10 10 10
n3-02
HSB Current
Limit Level
1 150 120 150 120 150 120 150 120
n5-02
Motor Inertia
Acceleration
Time
s 0.178 0.178 0.178 0.142 0.178 0.142 0.142 0.142
*1 Parameters within parentheses are for motor 2.
No.
*1
Name Unit Default
- Drive Model - 2010 2012 2021 2030
C6-01
Normal /
Heavy Duty
Selection
-
HD ND HD ND HD ND HD ND
0 1 0 1 0 1 0 1
o2-04
Drive Model
(KVA)
Selection
Hex. 65 66 68 6A
E2-11
(E4-11, E5-
02)
Motor Rated
Power
kW 1.5 2.2 2.2 3.0 3.7 5.5 5.5 7.5
b3-04
V/f Gain
during Speed
Search
% 100 100 100 100 100 100 100 100
b3-06
Speed
Estimation
Current Level
1
- 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
b3-08
Speed
Estimation
ACR P Gain
- 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
b3-26
Direction
Determination
Level
- 1000 1000 1000 1000 1000 1000 1000 1000
b8-03
Energy Saving
Filter Time
s 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
b8-04
Energy Saving
Coefficient
Value
- 169.4 156.8 156.8 136.4 122.9 94.75 94.75 72.69
C6-02
Carrier
Frequency
Selection
- 3 7 3 7 3 7 3 7
E2-01
(E4-01)
Motor Rated
Current (FLA)
A 6.2 8.5 8.5 11.4 14 19.6 19.6 26.6