EasyManua.ls Logo

YASKAWA GA500 GA50U Series

YASKAWA GA500 GA50U Series
524 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter List
1
1.21 Defaults by Drive Model and Duty Rating ND/HD
YASKAWA TOEPYAIGA5002A GA500 DRIVE PROGRAMMING 135
No.
*1
Name Unit Default
- Drive Model - 2010 2012 2021 2030
C6-01
Normal /
Heavy Duty
Selection
-
HD ND HD ND HD ND HD ND
0 1 0 1 0 1 0 1
o2-04
Drive Model
(KVA)
Selection
Hex. 65 66 68 6A
E2-11
(E4-11, E5-
02)
Motor Rated
Power
kW 1.5 2.2 2.2 3.0 3.7 5.5 5.5 7.5
E2-02
(E4-02)
Motor Rated
Slip
Hz 2.6 2.9 2.9 2.7 2.73 1.5 1.5 1.3
E2-03
(E4-03)
Motor No-
Load Current
A 2.8 3 3 3.7 4.5 5.1 5.1 8
E2-05
(E4-05)
Motor Line-to-
Line
Resistance
Ω 1.997 1.601 1.601 1.034 0.771 0.399 0.399 0.288
E2-06
(E4-06)
Motor
Leakage
Inductance
% 18.5 18.4 18.4 19 19.6 18.2 18.2 15.5
E2-10
(E4-10)
Motor Iron
Loss
W 53 77 77 91 112 172 172 262
E5-01
PM Motor
Code Selection
- FFFF FFFF FFFF FFFF FFFF FFFF FFFF FFFF
L2-02
Power Loss
Ride Through
Time
s 0.3 0.3 0.5 0.5 1 1 1 1
L2-03
Minimum
Baseblock
Time
s 0.4 0.5 0.5 0.5 0.6 0.7 0.7 0.8
L2-04
Powerloss V/f
Recovery
Ramp Time
s 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3
L2-05
Undervoltage
Detection Lvl
(Uv1)
- 190 190 190 190 190 190 190 190
L3-02
Stall Prevent
Level during
Accel
% 150 120 150 120 150 120 150 120
L3-06
Stall Prevent
Level during
Run
% 150 120 150 120 150 120 150 120
L3-24
Motor Accel
Time @ Rated
Torque
s 0.166 0.145 0.145 0.145 0.154 0.168 0.168 0.175
L8-02
Overheat
Alarm Level
°C 110 110 110 110 115 115 105 105
L8-09
Output Ground
Fault
Detection
- 0 0 0 0 0 0 1 1
n1-03
Hunting
Prevention
Time Constant
ms 10 10 10 10 10 10 10 10
n3-02
HSB Current
Limit Level
1 150 120 150 120 150 120 150 120
n5-02
Motor Inertia
Acceleration
Time
s 0.166 0.145 0.145 0.145 0.154 0.168 0.168 0.175
*1 Parameters within parentheses are for motor 2.

Table of Contents

Related product manuals