3.20 Parameters Changed by E1-03 [V/f Pattern Selection]
280 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance & Troubleshooting
Table 3.2 Parameters Changed by E1-03: 2030 to 2211 (HD), 2021 to 2169 (ND), 4018 to 4103 (HD), 4012 to 4089 (ND), and
T103 (HD)
No. E1-03 E1-04 E1-05
*1
E1-06 E1-07 E1-08
*1
E1-09 E1-10
*1
Unit - Hz V Hz Hz V Hz V
Setting Value
0 50.0 230.0 50.0 2.5 16.1 1.3 8.1
1 60.0 230.0 60.0 3.0 16.1 1.5 8.1
2 60.0 230.0 50.0 3.0 16.1 1.5 8.1
3 72.0 230.0 60.0 3.0 16.1 1.5 8.1
4 50.0 230.0 50.0 25.0 40.3 1.3 6.9
5 50.0 230.0 50.0 25.0 57.5 1.3 8.1
6 60.0 230.0 60.0 30.0 40.3 1.5 6.9
7 60.0 230.0 60.0 30.0 57.5 1.5 8.1
8 50.0 230.0 50.0 2.5 20.7 1.3 10.4
9 50.0 230.0 50.0 2.5 26.5 1.3 12.7
A 60.0 230.0 60.0 3.0 20.7 1.5 10.4
B 60.0 230.0 60.0 3.0 26.5 1.5 15.0
C 90.0 230.0 60.0 3.0 16.1 1.5 8.1
D 120.0 230.0 60.0 3.0 16.1 1.5 8.1
E 180.0 230.0 60.0 3.0 16.1 1.5 8.1
F 60.0
*2
230.0
*2
60.0
*2
3.0
*2
16.1
*2
1.5
*2
8.1
*2
Control Method
Selection
(A1-02 Setting)
OLV (2) 60.0 230.0 60.0 3.0 12.7 0.5 2.3
CLV (3) 60.0 230.0 60.0 0.0 0.0 0.0 0.0
OLV/PM (5)
*3 *3 *3
- -
*3
-
AOLV/PM (6)
*3 *3 *3
- -
*3
-
CLV/PM (7)
*3 *3 *3
- - 0.0 -
*1 This is the value for 200 V class drives. Double the value for 400 V class drives.
*2 These values are the default settings for E1-04 to E1-10 and E3-04 to E3-10 [V/f Pattern for Motor 2]. These settings are the same as
those for the V/f pattern when E1-03 = 1 [Const Trq, 60Hz base, 60Hz max].
*3 The default setting varies depending on the setting of E5-01 [PM Motor Code Selection].