Parameter List
3
3.21 Defaults by Drive Model and Duty Rating ND/HD
YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance & Troubleshooting 291
No.
*1
Name Unit Default
- Drive Model - 4002 4004 4005 4007
C6-01
Normal /
Heavy Duty
Selection
-
HD ND HD ND HD ND HD ND
0 1 0 1 0 1 0 1
o2-04
Drive Model
(KVA)
Selection
Hex. 0092 0093 0094 0095
E2-11
(E4-11, E5-
02)
Motor Rated
Power
HP
(kW)
0.75
(0.4)
1
(0.75)
1
(1.1)
2
(1.5)
2
(1.5)
3
(2.2)
3
(2.2)
4
(3.0)
L3-24
Motor Accel
Time @ Rated
Torque
s 0.178 0.142 0.142 0.166 0.166 0.145 0.145 0.145
L8-02
Overheat
Alarm Level
°C 100 100 105 105 112 112 100 100
L8-09
Output Ground
Fault
Detection
- 1 1 1 1 1 1 1 1
L8-38
Carrier
Frequency
Reduction
- 2 2 2 2 2 2 2 2
n1-01
Hunting
Prevention
Selection
- 1 1 1 1 1 1 1 1
n1-03
Hunting
Prevention
Time Constant
ms 10 10 10 10 10 10 10 10
n1-16
Hunting
Prevention
High Fc Gain
- 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50
n5-02
Motor Inertia
Acceleration
Time
s 0.178 0.142 0.142 0.166 0.166 0.145 0.145 0.145
*1 Parameters within parentheses are for motor 2.
No.
*1
Name Unit Default
- Drive Model - 4009 4012 4018 4023
C6-01
Normal /
Heavy Duty
Selection
-
HD ND HD ND HD ND HD ND
0 1 0 1 0 1 0 1
o2-04
Drive Model
(KVA)
Selection
Hex. 0096 0097 0099 009A
E2-11
(E4-11, E5-
02)
Motor Rated
Power
HP
(kW)
4
(3.0)
5
(4.0)
5
(4.0)
7.5
(5.5)
7.5
(5.5)
10
(7.5)
10
(7.5)
15
(11)
b3-04
V/f Gain
during Speed
Search
% 100 100 100 100 100 100 100 100
b3-06
Speed
Estimation
Current Level
1
- 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
b3-08
Speed
Estimation
ACR P Gain
- 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
b3-26
Direction
Determination
Level
- 1000 1000 1000 1000 1000 1000 1000 1000
b8-03
Energy Saving
Filter Time
s 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50
b8-04
Energy Saving
Coefficient
Value
- 265.7 245.8 245.8 189.5 189.5 145.38 145.38 140.88
C5-17
(C5-37)
Motor Inertia kgm
2
0.0158 0.0158 0.0158 0.0255 0.026 0.037 0.037 0.053