Parameter List
3
3.21 Defaults by Drive Model and Duty Rating ND/HD
YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance & Troubleshooting 295
No.
*1
Name Unit Default
- Drive Model - 4075 4089 4103 4140
C6-01
Normal /
Heavy Duty
Selection
-
HD ND HD ND HD ND HD ND
0 1 0 1 0 1 0 1
o2-04
Drive Model
(KVA)
Selection
Hex. 00A1 00A2 00A3 00A4
E2-11
(E4-11, E5-
02)
Motor Rated
Power
HP
(kW)
40
(30)
50
(37)
50
(37)
60
(45)
60
(45)
75
(55)
75
(55)
100
(75)
E2-02
(E4-02)
Motor Rated
Slip
Hz 1.8 1.33 1.33 1.6 1.6 1.46 1.46 1.39
E2-03
(E4-03)
Motor No-
Load Current
A 10.9 19.1 19.1 22 22 24 24 36
E2-05
(E4-05)
Motor Line-to-
Line
Resistance
Ω 0.269 0.155 0.155 0.122 0.122 0.088 0.088 0.092
E2-06
(E4-06)
Motor
Leakage
Inductance
% 20.7 18.8 18.8 19.9 19.9 20 20 20
E2-10
(E4-10)
Motor Iron
Loss
W 750 925 925 1125 1125 1260 1260 1600
E5-01
PM Motor
Code Selection
- 1242 1242 1243 1243 1244 1244 1245 1245
L2-02
Power Loss
Ride Through
Time
s 2 2 2 2 2 2 2 2
L2-03
Minimum
Baseblock
Time
s 1.1 1.1 1.1 1.2 1.2 1.2 1.2 1.3
L2-04
Powerloss V/f
Recovery
Ramp Time
s 0.6 0.6 0.6 0.6 0.6 1 1 1
L2-05
Undervoltage
Detection Lvl
(Uv1)
- 380 380 380 380 380 380 380 380
L3-24
Motor Accel
Time @ Rated
Torque
s 0.323 0.32 0.32 0.387 0.387 0.317 0.317 0.533
L8-02
Overheat
Alarm Level
°C 120 120 115 115 126 120 120 120
L8-09
Output Ground
Fault
Detection
- 1 1 1 1 1 1 1 1
L8-38
Carrier
Frequency
Reduction
- 2 2 2 2 2 2 2 2
n1-01
Hunting
Prevention
Selection
- 2 2 2 2 2 2 2 2
n1-03
Hunting
Prevention
Time Constant
ms 10 10 10 10 10 10 30 30
n1-16
Hunting
Prevention
High Fc Gain
- 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50
n5-02
Motor Inertia
Acceleration
Time
s 0.323 0.32 0.32 0.387 0.387 0.317 0.317 0.533
*1 Parameters within parentheses are for motor 2.