5.4 Main Circuit Terminal Block Wiring Procedure
378 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance & Troubleshooting
Figure 5.33 Permitted Angle
Put the bit all the way into the hex socket to tighten the hex socket cap screw.
When you tighten slotted screws, hold the straight-edge screwdriver perpendicularly to the screw. Make sure that
you align the end of the straight-edge screwdriver with the screw groove.
Figure 5.34 Tightening Slotted Screws
After you connect the wires to the terminal block, lightly pull on the wires to make sure that they do not come out
of the terminals.
Remove the correct section of the wiring cover to make wiring easier.
Do not let strain on the wiring cause damage. Use a strain relief near the wiring to release the tension. Refer to
Figure 5.35 for an example.
A - Cable clamp
Figure 5.35 Strain Relief Example
Table 5.6 Recommended Wiring Tools
Screw Size Screw Shape Adapter
Bit
Torque Driver Model
(Tightening Torque)
Torque Wrench
Model Manufacturer
M4 Bit SF-BIT-SL 1,0X4,0-70 PHOENIX CONTACT
TSD-M 3NM
(1.2 - 3 N∙m
(10.6 - 26.6 lbf∙in))
-
M5
*1
Bit SF-BIT-SL 1,2X6,5-70 PHOENIX CONTACT
Wire Gauge
25 mm
2
(AWG 10):
TSD-M 3NM
(1.2 - 3 N∙m
(10.6 - 26.6 lbf∙in))
Wire Gauge
25 mm
2
(AWG 10): -
Wire Gauge
30 mm
2
(AWG 8): -
Wire Gauge
30 mm
2
(AWG 8):
4.1 - 4.5 N∙m
(36.3 - 39.8 lbf∙in)
*2 *3