EasyManua.ls Logo

YASKAWA GA800

YASKAWA GA800
566 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1.5 Replace the Drive
68 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance & Troubleshooting
Connect the Control Circuit Terminal Block
1. To put a wired control circuit terminal block in the drive, align it with the guides and move it straight up.
A - Guides
Figure 1.94 Put the Terminal Block into the Connector
2. Use M3 screws to safety the terminal block.
Tighten the screws to a correct tightening torque:
M3 screws: 0.5 Nm to 0.6 Nm (4.4 lbfin to 5.3 lbfin)
Figure 1.95 Safety the Terminal Block
3. Install the front cover and the keypad to their initial positions.
4. Check o2-04 [Drive Model (KVA) Selection].
Note:
When you save parameter information in a keypad that you installed before you replaced the terminal block, make sure that you use that
keypad to restore the parameter data.
To reset the performance life monitors for the components, set o4-01 to o4-13 [Maintenance Period].