No. Parameter Name Setting Range Default
A2-33 User Parameter Automatic Selection 0 or 1 0
Setting 0: Do not save list of recently viewed parameters.
To manually select the parameters listed in the User Parameter group, set A2-33 to “0”.
Setting 1: Save history of recently viewed parameters.
By setting A2-33 to 1, all parameters that were recently edited will be automatically saved to A2-17 through A2-32. A total
of 16 parameters are saved in order with the most recently edited parameter set to A2-17. User parameters can be accessed
using the Setup mode of the digital operator.
5.1 A: Initialization
114
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual