B.17 Defaults by Drive Model
No. Description Unit Default Settings
− Model − BV0006 BV0010 BV0012 BV0018
o2-04 Drive Model Selection Hex 33 34 35 37
E2-11 Motor Rated Power kW 1.1 2.2 3.0 3.7
b3-06 Speed Search current 1 − 0.5 0.5 0.5 0.5
b3-08
Current Control Gain during Speed Search (Speed
Estimation Type)
– 0.5 0.5 0.5 0.5
C6-02 Carrier frequency − 7 7 7 3
E2-01 Motor rated current A 6.2 8.5 11.4 14.0
E2-02 Motor rated slip Hz 2.6 2.9 2.7 2.73
E2-03 Motor no-load current A 2.8 3 3.7 4.5
E2-05 Motor line-to-line resistance Ω 1.997 1.601 1.034 0.771
E2-06 Motor leakage inductance % 18.5 18.4 19 19.6
E2-10 Motor Iron Loss W 53 77 91 112
L2-02 Momentary power loss ride-through time s 0.2 0.3 0.5 1.0
L2-03 Momentary power loss Baseblock time s 0.4 0.5 0.5 0.6
L2-04 Momentary power loss voltage recovery time s 0.3 0.3 0.3 0.3
L2-05 Uv detection voltage V dc 160 160 160 160
L3-24 Motor acceleration time s 0.142 0.145 0.145 0.154
L8-02 Overheat alarm level °C 105 100 95 100
L8-09 Ground fault selection − 0 0 0 0
L8-38 Carrier frequency reduction selection − 1 1 1 1
n1-03 Hunting Prevention Time Constant ms 10 10 10 10
B.17 Defaults by Drive Model
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
377
B
Parameter List