Status Description
Open
REMOTE: The external reference that has been selected (either b1-01 and b1-02 or b1-15 and b1-16) is used as frequency reference
and Run command source.
Closed LOCAL: The digital operator is used as frequency reference and Run command source.
Setting 3D: During Speed Search
The output terminal closes while Speed Search is being performed.
Setting 3E: PID Feedback Low
Output terminal closes when a PID feedback loss (FbL) is detected. The feedback is considered to be lost if it falls below the
level set to b5-13 for longer than the time set to b5-14.
Setting 3F: PID Feedback High
Output terminal closes when a PID feedback loss (FbH) is detected. The feedback is considered to be lost if it rises beyond
the level set to b5-36 for longer than the time set to b5-37.
Setting 4A: During KEB Operation
Output terminal closes while KEB is being performed.
Setting 4C: During Fast Stop
Output terminal closes when a Fast Stop is being executed.
Setting 4D: oH Pre-Alarm Time Limit
Output terminal closes when the drive is reducing the speed due to a drive overheat alarm (L8-03 = 4) and the overheat alarm
has not disappeared after 10 frequency reduction operation cycles.
Setting 4E: Braking Transistor Fault (rr)
The output closes if the internal braking transistor reaches the overheat level.
Setting 4F: Braking Resistor Overheat (rH)
Output terminal closes when the braking resistor exceeds the overheat level. The braking resistor may overheat due to motor
regeneration or short deceleration time setting.
Setting 58: Underload Detection
Output terminal closes when the output current falls below the underload detection level defined by L6-14 and L6-02.
Setting 89: Output I Limit
Output terminal closes when drive output speed is being limited due to the output current limit or the single-phase foldback
regulator.
Setting 8B: Lube Pump or Digital Output Delay
Energizes for the time set in parameter P4-31 each time the drive is supposed to start. The drive will delay starting for the
P4-31 time.
Setting 8F: Internal Fan On
Output terminal closes when the internal fan is active.
Setting 91: Pump Fault
Output terminal closes when any of the following faults are active: Low Feedback, High Feedback, Low Water, High Water,
NMS-SetPoint Not Met, POC-Pump Over Cycle, THMS-Thermostat Input, External Pump Fault.
Setting 92: Transducer Loss
Output terminal closes the analog input associated with PID feedback has gone above 21mA or below 3mA, or a Transducer
Loss Alarm or Fault is active.
Setting 93: Setpoint Not Met
Output terminal closes during an “NMS – SetPoint Not Met” condition.
Setting 94: Loss of Prime
Output terminal closes during an “LOP – Loss Of Prime” condition.
Setting 95: Volute Thermostat Fault
Output terminal closes when Volute-Thermostat digital input is active.
5.7 H: Terminal Functions
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
181