EasyManua.ls Logo

YASKAWA iQpump Micro CIMR-PW Series - Page 184

YASKAWA iQpump Micro CIMR-PW Series
444 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
n
H3-09: Terminal A2 Signal Level Selection
Selects the input signal level for analog input A2. Set DIP Switch S1-2 on the terminal board accordingly for a voltage input
or current input.
No. Name Setting Range Default
H3-09 Terminal A2 Signal Level Selection 0 to 3 2
Setting 0: 0 to 10 Vdc
The input level is 0 to 10 Vdc.
Refer to Setting 0: 0 to 10 Vdc on page 182.
Setting 1: 0 to 10 Vdc Bipolar
The input level is -10 to 10 Vdc. Refer to Setting 1: 0 to 10 Vdc Bipolar on page 183.
Setting 2: 4 to 20 mA
The input level is 4 to 20 mA. Negative input values by negative bias or gain settings will be limited to 0%.
Setting 3: 0 to 20 mA
The input level is 0 to 20 mA. Negative input values by negative bias or gain settings will be limited to 0%.
n
H3-10: Terminal A2 Function Selection
Determines the function assigned to analog input terminal A2.
No. Name Setting Range Default
H3-10 Terminal A2 Function Selection 0 to 32 B
n
H3-11, H3-12: Terminal A2 Gain and Bias Setting
Parameter H3-11 sets the level of the input value selected that is equal to 10 Vdc input or 20 mA input to terminal A2.
Parameter H3-12 sets the level of the input value selected that is equal to 0 V, 4 mA or 0 mA input at terminal A2.
Use both parameters to adjust the characteristics of the analog input signal to terminal A2. The setting works in the same way
as parameters H3-03 and H3-04 for analog input A1.
No. Name Setting Range Default
H3-11 Terminal A2 Gain Setting -999.9 to 999.9% 100.0%
H3-12 Terminal A2 Bias Setting -999.9 to 999.9% 0.0%
n
H3-13: Analog Input Filter Time Constant
Parameter H3-13 sets the time constant for a first order filter that will be applied to both analog inputs A1 and A2.
No. Name Setting Range Default
H3-13 Analog Input Filter Time Constant 0.00 to 2.00 s 0.03 s
An analog input filter can be used to prevent erratic drive control when a “noisy” analog reference is used. The drive operation
becomes more stable the longer the time programmed, but it becomes less responsive to rapidly changing analog signals.
n
Multi-Function Analog Input Terminal Settings for A1 and A2 (H3-02 and H3-10)
This section describes the various functions that can be assigned to terminals A1 and A2 by setting H3-02 and H3-10.
Note: The scaling of all input functions depends on the gain and bias settings for the analog inputs. Set these to appropriate values when selecting
and adjusting analog input functions.
Table 5.25 Multi-Function Input Terminal Settings
Setting Function Page
0 Frequency Bias 185
1 Frequency Gain 185
2 Auxiliary Frequency Reference 185
4 Output Voltage Bias 185
7 Overtorque/Undertorque Detection Level 185
B PID Feedback 185
C PID Setpoint 185
Setting Function Page
E Motor Temperature (PTC input) 185
F Not Used 185
16 Differential PID Feedback 185
1F Not Used 185
20 HAND Frequency Reference 185
41 Output Voltage Gain 185
5.7 H: Terminal Functions
184
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual

Table of Contents

Related product manuals