Setting 0: Disabled
Setting 1: Enabled
n
Q3-11: Ripple Regulator Setpoint
Set as a percentage of the maximum amount of ripple allowed before an input phase loss fault is detected.
No. Name Setting Range Default
Q3-11 Ripple Regulator Setpoint 0.0 to 200.0% 95.0%
u
S6: Drive Protection
n
S6-01: Emergency Override Speed
Sets the sped command used in emergency override mode when S6-02 = 0.
No. Name Setting Range Default
S6-01 Emergency Override Speed 0.00 to 240.00 Hz 0.00 Hz
n
S6-02: Emergency Override Reference Selection
Selects the emergency override speed source.
No. Name Setting Range Default
S6-02 Emergency Override Reference Selection 0, 1 0
Setting 0: Use S6-01 Reference
Setting 1: Use Frequency Reference
u
T: Motor Tuning
Auto-Tuning automatically sets and tunes parameters required for optimal motor performance.
Refer to T: Motor Tuning on page 368 for details on Auto-Tuning parameters.
5.12 Q: PID Controller
246