LED Display LCD Display Fault Name
Cause Possible Solution
Hardware is damaged Replace the drive.
LED Display LCD Display Fault Name
cPF25
CPF25
Terminal Board Not Connected
Cause Possible Solution
Terminal board is not connected correctly Reconnect the terminal board to the connector on the drive, then cycle the power to the drive.
LED Display LCD Display Fault Name
cPF26
to
cPF35
_ _ _ _ _ _ _
cPF40
to
cPF43
CPF26
to
CPF35
_ _ _ _ _ _ _
CPF40
to
CPF43
Control Circuit Error
CPU error
Cause Possible Solution
Hardware is damaged Replace the drive.
LED Display LCD Display Fault Name
E5
E5
SI-T3 Watchdog Timer Error
The watchdog timed out.
Cause Possible Solution
Data has not been received from the PLC
Execute DISCONNECT or ALM_CLR, then issue a CONNECT command or SYNC_SET command and
proceed to phase 3. Refer to the SI-T3 Option Technical Manual for more details on troubleshooting.
LED Display LCD Display Fault Name
EF0
EF0
Option Card External Fault
An external fault condition is present.
Cause Possible Solution
An external fault was received from the PLC
and F6-03 is set to a value other than 3.
• Remove the cause of the external fault.
• Remove the external fault input from the PLC.
Problem with the PLC program Check the PLC program and correct problems.
LED Display LCD Display Fault Name
EF1
EF1
Pump Fault (input terminal S1)
External fault at multi-function input terminal S1.
EF2
EF2
Pump Fault (input terminal S2)
External fault at multi-function input terminal S2.
EF3
EF3
Pump Fault (input terminal S3)
External fault at multi-function input terminal S3.
EF4
EF4
Pump Fault (input terminal S4)
External fault at multi-function input terminal S4.
EF5
EF5
Pump Fault (input terminal S5)
External fault at multi-function input terminal S5.
EF6
EF6
Pump Fault (input terminal S6)
External fault at multi-function input terminal S6.
EF7
EF7
Pump Fault (input terminal S7)
External fault at multi-function input terminal S7.
Cause Possible Solution
An external device tripped an alarm function Remove the cause of the external fault and reset the fault.
Wiring is incorrect
• Properly connect the signal lines to the terminals assigned for external fault detection
(H1-oo = 20 to 2F).
• Reconnect the signal line.
6.3 Fault Detection