Name LCD Display Description Values Page
L8-35
(04EC)
Installation Method
Selection
Installation Sel
0: IP00/OpenChassis
1: Side-by-Side
2: IP20/Nema 1, UL
Type 1
3: ExternalHeatsink
0: IP00/Open-Chassis enclosure
1: Side-by-Side mounting
2: IP20/NEMA 1, UL Type 1 enclosure
3: Finless model drive or external heatsink installation
Default:
<1> <2>
Range: 0 to 3
211
L8-38
(04EF)
Carrier Frequency
Reduction
Fc Reduct dur OL
0: Disabled
1: Active below 6Hz
2: Active @ any Spd
0: Disabled
1: Enabled below 6 Hz
2: Enabled for the entire speed range
Default: 1
Range: 0 to 2
211
L8-40
(04F1)
Carrier Frequency
Reduction Off Delay
Time
Fc Reduct Time
Sets the time that the drive continues running with reduced
carrier frequency after the carrier reduction condition is gone.
Setting 0.00 s disables the carrier frequency reduction time.
Default: 0.50 s
Min.: 0.00
Max.: 2.00
212
L8-41
(04F2)
High Current Alarm
Selection
High Cur Alm Sel
0: Disabled
1: Enabled
0: Disabled
1: Enabled. An alarm is triggered at output currents above 150%
of drive rated current.
Default: 0
Range: 0, 1
212
<1> Default setting is dependent on parameter o2-04, Drive Model Selection.
<2> Parameter setting value is not reset to the default value when the drive is initialized.
B.9 L: Protection Function
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual