No.
(Addr.
Hex)
Name LCD Display Description
Analog
Output Level
Unit
U1-19
(0066)
MEMOBUS/Modbus
Error Code
Transmit Err
Displays the contents of a MEMOBUS/Modbus error.
U1
-
19=
00000000
CRC Error
Data Length Error
Not Used
Parity Error
Overrun Error
Framing Error
Timed Out
Not Used
1
1
0
1
1
1
1
0
CRC Error
Data Length Error
Not Used
Parity Error
Overrun Error
Framing Error
Timed Out
Not Used
No signal output
available
–
U1-24
(007D)
Input Pulse Monitor Term RP Inp Freq
Displays the frequency to pulse train input terminal RP. Determined by
H6-02
1 Hz
U1-25
(004D)
Software Number
(Flash)
CPU 1 SW Number
FLASH ID No signal output
available
–
U1-26
(005B)
Software No. (ROM) CPU 2 SW Number
ROM ID No signal output
available
–
U1-75
(0851)
Time-Hour/Minute Time Hr Min HHMM
Displays the current time (Hours and Minutes). No signal output
available
–
U1-76
(0852)
Date – Year Date Year
Displays the current year. No signal output
available
–
U1-77
(0853)
Date – Month/Day Date Mo Day MMDD
Displays the current date (Month and Date). No signal output
available
–
U1-78
(0854)
Date – Week Day Date Week
Displays the current day of the week.
0: Sunday
1: Monday
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
No signal output
available
–
U1-90
(0BA5)
Pump Setpoint Pump Setpoint
Displays the PID Setpoint. No signal output
available
dep. on
P1-02
U1-91
(0BA6)
Pump Feedback Pump Feedback
Displays the PID Feedback. No signal output
available
dep. on
P1-02
U1-93
(0BA8)
Total Setpoint
Compensation
Total SP Comp.
Displays the total absolute Setpoint Compensation. No signal output
available
dep. on
P1-02
U1-94
(0BA9)
Motor Speed Motor Speed
Displays the absolute value of the output frequency (U1-02)
converted to RPM.
No signal output
available
1 RPM
U1-99
(0BAE)
Anti-No-Flow Timer ANF Timer
The Anti-No-Flow reduces the output frequency when this
value reaches the P2-24 setting.
No signal output
available
0.1 s
<1> Display is in the following units:
BV0006 to BV0018, 2V0006 to 2V0040, and 4V0002 to 4V0023: 0.01 A units.
2V0056 to 2V0069 and 4V0031 to 4V0038: 0.1 A units.
<2> When reading the value of this monitor via MEMOBUS/Modbus, a value of 8192 is equal to 100% of the drive rated output current.
<3> Values shown are specific to 200 V class drives. Double the value for 400 V class drives.
<4> This value has two decimal places (0.01 kW) if the drive is set for a maximum applicable motor capacity up to and including 11 kW, and one
decimal place (0.1 kW) if the maximum applicable motor capacity is higher than 11 kW.
B.16 U: Monitors
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
371
B
Parameter List