Drive Model
Non-time Delay
Fuse Rating (A)
<1>
Time Delay Fuses
Bussmann
Semiconductor
Fuse Part Number
(Fuse Ampere)
<4>
MCCB
<5>
Class J, T, or CC
Fuse Rating (A)
<2>
Class RK5
Fuse Rating (A)
<3>
Rating (A)
Minimum
Enclosure
Volume (in
3
)
2V0040 – 90 110 FWH-200B (200) 125 1152
2V0056 – 110 150 FWH-200B (200) 150 2560
2V0069 – 125 175 FWH-200B (200) 200 2560
400 V Class Three-Phase Drives
4V0002 6 3.5 3 FWH-40B (40) 15 1152
4V0004
15
<7>
7 8 FWH-50B (50) 15 1152
4V0005
20
<8>
10 10 FWH-70B (70) 15 1152
4V0007
25
<9>
12 15 FWH-70B (70) 20 1152
4V0009 25 15 20 FWH-90B (90) 20 1152
4V0011 30 20 30 FWH-90B (90) 35 1152
4V0018 – 35 45 FWH-80B (80) 50 1152
4V0023 – 40 50 FWH-100B (100) 60 1152
4V0031 – 60 80 FWH-125B (125) 90 1152
4V0038 – 70 90 FWH-200B (200) 110 1152
<1> Maximum 300% of drive input current rating for any Class J, T, or CC fuse except for models 4V0004, 4V0005, and 4V0007.
<2> Maximum 175% of drive input current rating for any Class J, T, or CC fuse.
<3> Maximum 225% of drive input current rating for any Class RK5 fuse.
<4> When using semiconductor fuses, Bussmann FWH are required for UL compliance.
<5> Maximum MCCB Rating is 15 A or 200% of drive input current rating, whichever is larger. MCCB voltage rating must be 600 Vac or greater.
Additionally, when using MCCBs for protection, the drive must be installed in a ventilated enclosure with minimum volume according the “Minimum
Enclosure Volume” column.
<6> Model 4V0004 requires Mersen (Ferraz) part number A6T15 for compliance.
<7> Model 4V0005 requires Mersen (Ferraz) part number A6T20 for compliance.
<8> Model 4V0007 requires Mersen (Ferraz) part number A6T25 for compliance.
n
Low Voltage Wiring for Control Circuit Terminals
Wire low voltage wires with NEC Class 1 circuit conductors. Refer to national state or local codes for wiring. The external
power supply shall be a UL-Listed Class 2 power source or equivalent.
Table D.16 Control Circuit Terminal Power Supply
Input / Output Terminal Signal Power Supply Specifications
Multi-function photocoupler output P1, P2, PC Requires class 2 power supply
Multi-function digital inputs S1, S2, S3, S4, S5, S6, S7, SC
Use the internal power supply of the drive. Use class 2 for
external power supply.
Multi-function analog inputs A1, A2, AC
Use the internal power supply of the drive. Use class 2 for
external power supply.
Pulse train input RP
Use the internal LVLC power supply of the drive. Use class
2 for external power supply.
Pulse train output MP
Use the internal LVLC power supply of the drive. Use class
2 for external power supply.
n
Drive Short-Circuit Rating
This drive has undergone the UL short-circuit test, which certifies that during a short circuit in the power supply the current
flow will not rise above 31,000 amps maximum at 240 V for 200 V class drives and 480 V for 400 V class drives.
• The MCCB and breaker protection and fuse ratings shall be equal to or greater than the short-circuit tolerance of the power
supply being used.
• Suitable for use on a circuit capable of delivering not more than 31,000 RMS symmetrical amperes for 240 V in 200 V class
drives (up to 480 V for 400 V class drives) motor overload protection.
D.1 UL Standards
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
439
D
Standards Compliance