1 English
YASKAWA TOMPYEULA5001C LA500 Installation and Operation Instructions 15
◆ Overview of Keypad Components and Functions
Figure 1.5 Keypad
Table 1.1 Keypad Components and Functions
Symbol Name Function
A
USB Terminal Pass-
through
Pass-through point to connect a USB cable to the drive to support the DriveWizard PC
tool and the DriveWizard Mobile App. Uses a USB cable (USB standard 2.0, type A -
mini-B) to connect the drive to a PC, Android smartphone, or tablet.
B
RUN Key
Starts the drive in LOCAL Mode.
Starts the operation in Auto-Tuning Mode.
Note:
Before you use the keypad to operate the motor, push on the keypad to set the
drive to LOCAL Mode.
C
STOP Key
Stops drive operation.
Note:
Uses a stop-priority circuit. Push to stop the motor. This will also apply when a
Run command (REMOTE Mode) is active at an external Run command source. To
disable priority, set o2-02 = 0 [STOP Key Function Selection = Disabled].
D
LO/RE LED
Illuminated: The keypad controls the Run command (LOCAL Mode).
OFF: The control circuit terminal or serial transmission device controls the Run
command (REMOTE Mode).
Note:
• LOCAL: Use the keypad to operate the drive. Use the keypad to enter Run/Stop
commands and the frequency reference command.
• REMOTE: Use the control circuit terminal or serial transmission to operate the
drive. Use the Run command source selected in b1-02.