YASKAWA TOMPYEULA5001C LA500 Installation and Operation Instructions 35
Figure 1.11 Symmetric Grounding
NOTICE
Damage to Equipment. When you use the drive with a non-grounding, high-resistance
grounding, or asymmetric-grounding network, put the EMC Filter screw or screws in the OFF position to disable
the built-in EMC filter. If you do not disable the built-in EMC filter, it will cause damage to the drive.
If you lose an EMC filter switch screw, use Table 1.9 to find the correct replacement screw and
install the new screw with the correct tightening torque.
NOTICE
Only use the screws specified in this manual. If you use screws that are not approved, it
can cause damage to the drive.
Table 1.9 Screw Sizes and Tightening Torques
Model Screw Size
Tightening Torque
N∙m (in∙lb)
2018
4009
M3 × 20
0.5 - 0.6
(4.4 - 5.3)
2025 - 2075
4015 - 4045
M4 × 20
1.2 - 1.5
(10.6 - 13.3)
◆ Safe Disable Input
■ Overview
This section gives precautions to support the Safe Disable input. Contact Yaskawa for more
information.
The safety function complies with the standards shown in Table 1.10.
Table 1.10 Applied Unified Standards
Function Unified Standards
Functional
Safety
EN 62061 (SILCL3)
EN 61800-5-2 (SIL3)
Machine Safety
ISO/EN ISO 13849-1:2015 (Cat.3, PL e)
EMC
EN 61800-3
LVD
EN 61800-5-1
Note:
SIL = Safety Integrity Level.