268 YASKAWA TOMPYEULA5001C LA500 Installation and Operation Instructions
■ Three-Phase 400 V Class
Model Terminal
Recomm.
Gauge
mm
2
Applicable
Gauge
mm
2
Wire
Stripping
Length
*1
mm
Terminal Screw
Tightening
Torque
N∙m (in∙lb)
Size Shape
4009
R/L1, S/L2, T/L3 2.5 2.5 - 4 10 M4
1.5 - 1.7
(13.5 - 15)
U/T1, V/T2, W/T3 2.5 2.5 - 4 10 M4
1.5 - 1.7
(13.5 - 15)
-, +1, +2 2.5 2.5 - 4 10 M4
1.5 - 1.7
(13.5 - 15)
B1, B2 2.5 2.5 - 4 10 M4
1.5 - 1.7
(13.5 - 15)
4
*2
2.5 - 6
*2
- M4
1.2 - 1.5
(10.6 - 13.3)
4015
R/L1, S/L2, T/L3 2.5 2.5 - 4 10 M4
1.5 - 1.7
(13.5 - 15)
U/T1, V/T2, W/T3 2.5 2.5 - 4 10 M4
1.5 - 1.7
(13.5 - 15)
-, +1, +2 4 2.5 - 6 10 M4
1.5 - 1.7
(13.5 - 15)
B1, B2 2.5 2.5 - 4 10 M4
1.5 - 1.7
(13.5 - 15)
4
*2
2.5 - 16 - M5
2.0 - 2.5
(17.7 - 22.1)
4018
R/L1, S/L2, T/L3 4 2.5 - 6 10 M4
1.5 - 1.7
(13.5 - 15)
U/T1, V/T2, W/T3 4 2.5 - 6 10 M4
1.5 - 1.7
(13.5 - 15)
-, +1, +2 4 4 - 6 10 M4
1.5 - 1.7
(13.5 - 15)
B1, B2 2.5 2.5 - 4 10 M4
1.5 - 1.7
(13.5 - 15)
4
*2
4 - 16 - M5
2.0 - 2.5
(17.7 - 22.1)