YASKAWA TOMPYEULA5001C LA500 Installation and Operation Instructions 267
Model Terminal
Recomm.
Gauge
mm
2
Applicable
Gauge
mm
2
Wire
Stripping
Length
*1
mm
Terminal Screw
Tightening
Torque
Nm (inlb)
Size Shape
2047
R/L1, S/L2, T/L3 16 4 - 25 18 M5
2.3 - 2.5
(19.8 - 22)
U/T1, V/T2, W/T3 16 4 - 25 18 M5
2.3 - 2.5
(19.8 - 22)
-, +1, +2 25 6 - 35 18 M5
25 mm
2
2.3 - 2.5
(19.8 - 22)
35 mm
2
4.1 - 4.5
(36 - 40)
B1, B2 10 4 - 16 10 M4
1.5 - 1.7
(13.5 - 15)
10 10 - 25 - M6
5.4 - 6.0
(47.8 - 53.1)
2060
R/L1, S/L2, T/L3 25 6 - 35 20 M6
5 - 5.5
(45 - 49)
U/T1, V/T2, W/T3 16 6 - 25 20 M6
5 - 5.5
(45 - 49)
-, +1, +2 35 10 - 50 20 M6
5 - 5.5
(45 - 49)
B1, B2 10 4 - 16 10 M4
1.5 - 1.7
(13.5 - 15)
16 10 - 25 - M6
5.4 - 6.0
(47.8 - 53.1)
2075
R/L1, S/L2, T/L3 35 10 - 50 20 M6
5 - 5.5
(45 - 49)
U/T1, V/T2, W/T3 25 10 - 35 20 M6
5 - 5.5
(45 - 49)
-, +1, +2 50 16 - 70 20 M6
5 - 5.5
(45 - 49)
B1, B2 16 4 - 16 10 M4
1.5 - 1.7
(13.5 - 15)
16 10 - 25 - M6
5.4 - 6.0
(47.8 - 53.1)
*1 Remove insulation from the ends of wires to expose the length of wire shown.
*2 If you turn on the internal EMC filter, the leakage current of the drive will be more than 3.5 mA. Use the closed-
loop crimp terminals to connect a protective ground wire that has a minimum cross-sectional area of 10 mm
2
(copper wire).