Event ID Description
ZInfo3 : Output data width of the plugged module
0xEA10 SBUS: Input periphery address outside the periphery area
ZInfo1 : Periphery address
ZInfo2 : Slot
ZInfo3 : Data width
0xEA11 SBUS: Output periphery address outside the periphery area
ZInfo1 : Periphery address
ZInfo2 : Slot
ZInfo3 : Data width
0xEA12 SBUS: Error at writing record set
ZInfo1 : Slot
ZInfo2 : Record set number
ZInfo3 : Record set length
0xEA14 SBUS: Multiple parametrization of a periphery address (diagnostics address)
ZInfo1 : Periphery address
ZInfo2 : Slot
ZInfo3 : Data width
0xEA15 Internal error - Please contact the hotline!
0xEA18 SBUS: Error at mapping of the master periphery
ZInfo2 : Slot of the master
0xEA19 Internal error - Please contact the hotline!
0xEA1A SBUS: Error at access to the FPGA address table
ZInfo2 : HW slot
ZInfo3 : Table
0: Reading
1: Writing
PK : Not relevant to the user
DatID : Not relevant to the user
0xEA20 Error - RS485 interface is not pre-set to PROFIBUS DP master bus a PROFIBUS DP master is configured
0xEA21 Error - Configuration RS485 interface X2/X3: PROFIBUS DP master is configured but missing.
ZInfo2 : Interface X is faulty configured.
0xEA22 Error - RS485 interface X2 - Value exceeds the limits
ZInfo2 : Project engineering for X2
0xEA23 Error - RS485 interface X3 - Value exceeds the limits
ZInfo2 : Project engineering for X3
0xEA24 Error - Configuration RS485 interface X2/X3: Interface/protocol missing, default settings are used.
ZInfo2 : Project engineering for X2
ZInfo3 : Project engineering for X3
VIPA System MICRO
System specific event IDs
HB400 | CPU | M13-CCF0000 | en | 16-47 223