• Overtorque detection function selection (n50)
Setting Description
0 Overtorquedetection not provided
Detectedduring constant-speed running,
1 andoperation continues after detection.
2 Detectedduring constant-speed running,
and operation stops during detection.
Detected during running,
3 and operation continues after detection.
Detectedduring running,
4 and operation stops during detection.
(1) To detect overtorque at accel/deeel, set to 3 or 4.
(2) To continue the operation after overtorque detection, set to 1 or 3.
During detection, the operator displays "_/_ 3" alarm (blinking).
(3) To halt the inverter by a fault at overtorque detection, set to 2 or 4. At
detection, the operator displays ",rag.. 3" fault (ON).
• Overtorque detection level (n51)
Sets the overtorque detection current level in units of 1%. (Inverter rated
current = 100%)
Factory setting: 160%
• Overtorque detection time (n52)
If the time when motor current exceeds the overtorque detection level
(n51) is longer than overtorque detection time (n52), the overtorque
detection function operates.
36