Selecting Stopping Method
I Selecting stopping method (nO3) I
Selects the stopping method suitable for application.
,Setting Description
0 Deceleration to stop I
1 ICoast to stop
Deceleration to stop
Example when accel/decel lime I is selected
ACCEL DECELTIME1 MIN.OUTPUT
OUTPUT TIME! OECEL In2) FREQUENCY \
FREQUENCYI!n201 ,TIMEI / (FREQUENCYAT
In21) . _J OC INJECTIONBRAKINGCINGi
I
n29ST'RT'
! TIME (FACTORYSETTING:I,SHzI
DC INJECTION BRAKING
FWD (REVI_ ON
BUN TIMEATSTOP(n47I
COMMAND (FACTORYSETTING:0.5s)
Upon removal of the FWD (REV) run command, the motor decelerates at
the decel rate determined by the time set to decel time 1 (n21) and DC
injection braking is applied immediately before stop. If the decel time is
short or the load inertia is large, overvohage (OV) fault may occur at
deceleration. In this case, increase the decel time or install a optional
braking resistor.
Braking torque : Without braking resistor : Approx. 20% torque of motor rating
With braking resistor: Approx. 150% torque of motor
rating
44

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA VS mini C Series and is the answer not in the manual?

YASKAWA VS mini C Series Specifications

General IconGeneral
BrandYASKAWA
ModelVS mini C Series
CategoryInverter
LanguageEnglish

Related product manuals