Terminal Description
Name Function___
AC powersupply input L1(R) andN/L2 (S)forsingle-phasepowersupply
Inverteroutput For inverteroutput
Brakingresistorconnection For brakingresistorconnection
Forgrounding (groundingresistance should be
Grounding 100Qor less) -
Runs when CLOSED, stops
Fon_'ardrun/stop when OPEN
4
/
Reverse run/stop when OPEN -_24VDC8mA,
MultJ-fucotioncontactinput." FactoryI_eselis "Externallault Jinsulation"
(NOcontact)input" -I
Multi-fanctioncontactinput3 speedreference 1•
Sequence common input
+t 2V (allowaple current : max. 20mA)
Frequency reference input 0to t0VDC(20k.Q) or4to20mA(250_)
Frequency reference input OV
Factory resetis
Analogmonitoroutput* "Output_equency" ]O to 10VDC
0V ]2mA or less
J-.
"I
Factorypreset is JContantcapacity :
qCcontact output "Duringrunning" J25.0VAC..1Ao!less250VAC.1Aor less
3ontactoutputcommon
=holocoupleroutput Factorypreset is |PhtocoPhotocoupleroutput:
i
• Analog monitor is a terminal to monitor exclusively for frequency meter or ammeter.
Do not use it as a control signal for feedback control, etc.
The factory preset of signal level is 0 to +3VDC. By selling a constant, 0 to +IOVDC
output is available.
69