EasyManua.ls Logo

York MILLENNIUM YCAR0315 - FIG. 38 - Suction Pressure Cutout

York MILLENNIUM YCAR0315
160 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
120
YORK INTERNATIONAL
FORM 150.52-NM2 (1001)
New C.O.= Programmed C.O. x
(33.3 - Time Remaining)
33.3
This transient cutout value increases with time until af-
ter 30 seconds it equals the programmed cutout value.
If the suction pressure falls below the value as calcu-
lated by the formula relative to time, the system will
shut down on a low suction pressure fault. If the suc-
tion pressure rises above the programmed cutout value,
the 30-second timer will be reset.
If the Dip Switch on the microprocessor board is set
for “Water Cooling” (see page 124), the cutout is pro-
grammable between 3-5 bar (44-70 PSIG) for both R-
22 and R-407C models. In this mode, settings of 3 bar
(44 PSIG) for R-22 and R-407C are recommended. If
the Switch is set for “Brine Cooling” (glycol) the cut-
out is programmable between 0.3 - 5 bar (5 - 70 PSIG)
for R-22 and R-407C models. In this mode, the cutout
should typically be set to the saturated refrigerant pres-
sure equivalent to 10°C (18°F) below the temperature
of the chilled liquid. The sludge point of the glycol
MUST be at least another 11°C (20°F) below the
equivalent cutout temperature. This programmable
value is password protected.
High Compressor Motor Current Cutout:
The High Motor Current Safety protects against exces-
sively high motor current and shuts a system down and
locks it out after only a single occurrence of a rise in
average motor current above the cutout point. Motor
current is monitored through the 3 Current Transform-
ers (CTs) per motor, one on each phase, in the motor
protection module.
Average motor current is monitored after 4 seconds of
compressor operation. The system will be shut down if
average motor current exceeds 115% FLA.
FLA (full load amps) is approximately
1.2 x RLA (rated load amps). RLA is
specified on the motor / chiller name-
plate and is typical current demand
under rated operating conditions in a
fully loaded system. When a system is
fully loaded, typical motor currents
may be at 60 - 85% FLA depending on
operating conditions.
frigerant flow. A number of transient timer features pre-
vent nuisance trips during start-up, compressor loading,
etc. The Low Suction Pressure Safety is programmable
(see Section 9 [8.2] / Page 143, Low Suction Pressure
Cutout for more details).
The suction pressure cutout is ignored for the first 45
seconds of operation. During the next 180 seconds of
running , suction pressure may be lower than the cutout,
but must be greater than:
SP Cutout =
Programmed Cutout * (Run Time - 25)
200
This cutout value increases with time until after 225
seconds it equals the programmed cutout value. If suc-
tion pressure falls below the calculated cutout value
before 225 seconds of run time, the system will be shut
down.
The following graph shows a typical programmed suc-
tion pressure cutout of 3 bar (44 PSIG) and its change
from time = 0 sec of compressor run time to 225 sec-
onds of compressor run time.
After 225 seconds of operation with suction pressure
operating above the cutout, a 30-second transient timer
prevents short term fluctuations in suction pressure due
to loading or fan cycling from causing shutdown. If suc-
tion pressure drops below the cutout point after 225 sec-
onds of operation, the transient timer is activated. While
the transient timer is active, suction pressure must not
drop below 10% of the cutout initially programmed and
must be greater than:
Suction Pressure Cutout With
3 bar Programmed Cutout
LD03525
0 30 60 90 120 150 180 210 240 270 310
45
40
35
30
25
20
15
10
5
0
Run Time (seconds)
Suction Pressure Cutout
FIG. 38 – SUCTION PRESSURE CUTOUT
SYS # H I GH MTR CURR
SYS # H I GH MTR CURR
Micro Panel

Table of Contents

Related product manuals