FORM 150.52-NM2 (1001)
TEMPERATURES AND FLOWS
Technical Data
NOTES:
1. For leaving brine temperature below 4.4°C (40°F), contact your nearest YORK office for application requirements.
2. For leaving water temperature higher than 12.8°C (55°F), contact the nearest YORK office for application guidelines.
3. The evaporator is protected against freezing to -28.8°C (-20°F) with an electric heater as standard.
ENGLISH UNITS
MODEL LEAVING WATER COOLER FLOW AIR ON
NUMBER
TEMPERATURE (°F) (GPM
3
) CONDENSER (°F)
YCAR MIN.
1
MAX.
2
MIN. MAX. MIN. MAX
0315SC 40 55 125 600 0 125
0345SC 40 55 135 600 0 125
0365SC 40 55 144 600 0 125
0385SC 40 55 156 600 0 125
0415SC 40 55 180 600 0 125
0435SC 40 55 195 600 0 125
0485SC 40 55 213 747 0 125
0525SC 40 55 224 747 0 125
0575SC 40 55 247 747 0 125
0645SC 40 55 262 747 0 125
0685SC 40 55 277 747 0 125
SI UNITS
MODEL LEAVING WATER COOLER FLOW AIR ON
NUMBER
TEMPERATURE (°C) (L/S
3
) CONDENSER (°C)
YCAR MIN.
1
MAX.
2
MIN. MAX. MIN. MAX
0315SC 4.4 12.8 7.9 37.8 -17.7 51.7
0345SC 4.4 12.8 8.5 37.8 -17.7 51.7
0365SC 4.4 12.8 9.1 37.8 -17.7 51.7
0385SC 4.4 12.8 9.9 37.8 -17.7 51.7
0415SC 4.4 12.8 11.4 37.8 -17.7 51.7
0435SC 4.4 12.8 12.3 37.8 -17.7 51.7
0485SC 4.4 12.8 13.4 47.1 -17.7 51.7
0525SC 4.4 12.8 14.1 47.1 -17.7 51.7
0575SC 4.4 12.8 15.6 47.1 -17.7 51.7
0645SC 4.4 12.8 16.5 47.1 -17.7 51.7
0685SC 4.4 12.8 17.5 47.1 -17.7 51.7