20
YORK INTERNATIONAL
FORM 150.52-NM2 (1001)
Product Description
TABLE 1 – MOTOR PROTECTOR DIP SWITCH SETTINGS (ACROSS-THE-LINE START)
NO. OF LEADS
NO. OF LEADS MP OL *MP DIP
CHILLER VOLTS HZ RLA 100% FLA PER MOTOR
THRU MP VALUE SET SWITCHES
TERMINAL
YCAR0315
380 50 92 125 1 1 124 01111100
SYS. 1 AND 2
YCAR0345
SYS. 1 380 50 117 127 1 1 157 10011101
SYS. 2 380 50 92 100 1 1 124 01111100
YCAR0365
SYS. 1 AND 2 380 50 117 127 1 1 157 10011101
YCAR0385
SYS. 1 380 50 131 142 1 1 176 10110000
SYS. 2 380 50 117 127 1 1 157 10011101
YCAR0415
SYS. 1 AND 2 380 50 131 142 1 1 176 10110000
YCAR0435
SYS. 1 380 50 164 177 1 1 221 11011101
SYS. 2 380 50 131 142 1 1 176 10110000
YCAR0485
SYS. 1 AND 2
380 50 164 177 1 1 221 11011101
YCAR0525
SYS. 1 380 50 188 203 2 1 126 01111110
SYS. 2 380 50 164 177 1 1 221 11011101
YCAR0575
SYS. 1 AND 2
380 50 188 203 2 1 126 01111110
YCAR0645
SYS. 1 380 50 228 247 2 1 153 10011001
SYS. 2 380 50 188 203 2 1 126 01111110
YCAR0685
SYS. 1 AND 2
380 50 228 247 2 1 153 10011001
* “1” = ON