EasyManua.ls Logo

York MILLENNIUM YCAR0315 - Volts Free Contacts; System Inputs

York MILLENNIUM YCAR0315
160 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
35
YORK INTERNATIONAL
FORM 150.52-NM2 (1001)
VOLTS FREE CONTACTS
Chilled Liquid Pump Starter
Terminals 25 and 26 (Figures 11 and 12) close to start
the chilled liquid pump. This contact can be used as a
master start/stop for the pump in conjunction with the
daily start/stop schedule.
Run Contact
Terminals 29 and 30 (Figures 11 and 12) close to indi-
cate that a system is running.
Alarm Contacts
Each system has a voltage-free change over contact
which will operate to signal an alarm condition when-
ever a system locks out, or there is a power failure. To
obtain system alarm signal, connect the alarm circuit to
volt free terminals 23 and 24 (Figures 11 and 12) for
No. 1 System and to terminals 27 and 28 (Figures 11
and 12) for No.2 System.
SYSTEM INPUTS
Flow Switch
A chilled liquid flow switch of suitable type must be
connected to terminals 13 and 14 (Figures 11 and 12) to
provide adequate protection against loss of liquid flow.
Remote Run/Stop
Connect remote switch(es) in series with the flow switch
to provide remote run/stop control if required.
Remote Print
Closure of suitable contacts connected to terminals 13
and 18 (Figures 11 and 12) will cause a hard copy print-
out of Operating Data/Fault History to be made if an
optional printer is connected to the RS 232 port.
Remote Setpoint Offset – Temperature
Timed closure of suitable contacts connected to termi-
nals 13 and 17 (PWM contacts) will provide remote
offset function of the chilled liquid setpoint if required.
Remote Setpoint Offset – Current
Timed contact closure of a suitable contact connected
to terminals 13 and 16 (Figures 11 and 12) (PWM con-
tacts) will provide remote offset of EMS% CURRENT
LOAD LIMIT.
4

Table of Contents

Related product manuals