ELECTRICAL DATA
Technical Data
See page 53 for Electrical Data footnotes.
OPTIONAL SINGLE-POINT POWER SUPPLY WITH INTERNAL UNIT CIRCUIT BREAKERS (See Fig. 15)
(One Field Provided Power Supply Circuit to the chiller. Field connections to Power Terminal Block or Non-Fused Disconnect in ‘Option Panel’.
Internal Branch Circuit Protection (Breakers)
10
per Compressor)
CHILLER
FIELD-SUPPLIED WIRING
MODEL
VOLTS
FIELD PROVIDED POWER SUPPLY FACTORY PROVIDED (LUGS) WIRE RANGE
7
YCAR
MIN NF OVER-CURRENT PROTECTION
13
STANDARD OPTIONAL NF
MCA
1
DISC SW
2
MIN.
3, 5
MAX.
4, 6
TERMINAL BLOCK DISC. SWITCH
YCAR0315 380 230.3 250 300 300 2AWG - 300KCM 6AWG - 350KCM
YCAR0345 380 261.5 400 300 350 1/0 - 500KCM (2) 3/0 - 250KCM
YCAR0365 380 286.5 400 350 400 1/0 - 500KCM (2) 3/0 - 250KCM
YCAR0385 380 305.0 400 350 400 1/0 - 500KCM (2) 3/0 - 250KCM
YCAR0415 380 325.6 400 400 450 1/0 - 500KCM (2) 3/0 - 250KCM
YCAR0435 380 366.9 400 450 500 1/0 - 500KCM (2) 3/0 - 250KCM
YCAR0485 380 399.9 600 450 500 1/0 - 500KCM (2) 250KCM - 500KCM
YCAR0525 380 429.9 600 500 600 (2) 2AWG - 300KCM (2) 250KCM - 500KCM
YCAR0575 380 455.0 600 600 600 (2) 2AWG - 300KCM (2) 250KCM - 500KCM
YCAR0645 380 511.5 600 600 700 (2) 1/0 - 500KCM (2) 250KCM - 500KCM
YCAR0685 380 551.5 600 700 700 (2) 1/0 - 500KCM (2) 250KCM - 500KCM