Communication with Modbus
A43/A44 118 2CMC48001M0201
User Manual Revision: C
Quantity
Start Reg (Hex)
Size
Unit
Data type
3-Phase Sys. Power Factor
1016
2
*1000
Signed
Power Factor L1
1018
2
*1000
Signed
Power Factor L2
101A
2
*1000
Signed
Power Factor L3
101C
2
*1000
Signed
3-Phase Sys. Apparent Power
1026
2
VA
Unsigned
Apparent Power L1
1028
2
VA
Unsigned
Apparent Power L2
102A
2
VA
Unsigned
Apparent Power L3
102C
2
VA
Unsigned
3-Phase Sys. Active Power
102E
2
Watt
Signed
Active Power L1
1030
2
Watt
Signed
Active Power L2
1032
2
Watt
Signed
Active Power L3
1034
2
Watt
Signed
3-Phase Reactive power
1036
2
VAr
Signed
Reactive Power L1
1038
2
VAr
Signed
Reactive power L2
103A
2
VAr
Signed
Reactive Power L3
103C
2
VAr
Signed
3-Phase Sys. Active energy
103E
2
Wh*100
Unsigned
3-Phase Sys. Reactive energy
1040
2
VArh*100
Unsigned
Frequency
1046
2
mHz
Unsigned
Current transformer ratio (current
11A0
2
1-999999
Unsigned
transformer ratio secondary
current must be set to 1)
Voltage transformer ratio
11A2
2
1-9999
Unsigned
(voltage transformer ratio
secondary voltage must be set to
1)