Communication with M-Bus
A43/A44 208 2CMC48001M0201
User Manual Revision: C
Byte No.
Size
Value
Description
115
1
FF
VIF next byte is manufacturer specific
116
1
CA
VIFE phase angle current with resolution 0.1
117
1
FA
VIFE next byte is manufacturer specific
118
1
81
VIFE L1
119
1
xx
VIFE status
120-121
2
xxxx
Phase angle current, L1
122
1
02
DIF size, 16 bit integer
123
1
FF
VIF next byte is manufacturer specific
124
1
CA
VIFE phase angle current with resolution 0.1
125
1
FF
VIFE next byte is manufacturer specific
126
1
82
VIFE L2
127
1
xx
VIFE status
128-129
2
xxxx
Phase angle current, L2
130
1
02
DIF size, 16 bit integer
131
1
FF
VIF next byte is manufacturer specific
132
1
CA
VIFE phase angle current with resolution 0.1
133
1
FF
VIFE next byte is manufacturer specific
134
1
83
VIFE L3
135
1
xx
VIFE status
136-137
2
xxxx
Phase angle current, L3
138
1
8E
DIF size, 12 digit BCD
139
1
80
DIFE,
140
1
40
DIFE, unit 2
141
1
84
VIF for units kvarh with resolution 0,01kvarh
142
1
xx
VIFE status
143-148
6
xxxxxxxxxxxx
Reactive imported energy, Total
149
1
8E
DIF size, 12 digit BCD
150
1
90
DIFE, tariff 1
151
1
40
DIFE, unit 2
152
1
84
VIF for units kvarh with resolution 0,01kvarh
153
1
xx
VIFE status
154-159
6
xxxxxxxxxxxx
Reactive imported energy, Tariff 1
160
1
8E
DIF size, 12 digit BCD
161
1
A0
DIFE, tariff 2
162
1
40
DIFE, unit 2
163
1
84
VIF for units kvarh with resolution 0,01kvarh
164
1
xx
VIFE status
165-170
6
xxxxxxxxxxxx
Reactive imported energy, Tariff 2
171
1
8E
DIF size, 12 digit BCD
172
1
B0
DIFE, tariff 3
173
1
40
DIFE, unit 2