66 Diagnostics
EN
ES
FI
FR
IT
PL
PT
RU
SV
TR
ZH
8007 The application contains the wrong
system library version.
Update the system library or reinstall
Automation Builder.
See the drive-specific log generated
by Automation Builder.
8008 The application is empty. In Automation Builder, give a “Clean”
command and reload the application.
8009 The application contains invalid
tasks.
In Automation Builder, check
application task configuration, give a
“Clean all” command, and reload the
application.
800A The application contains an unknown
target (system) library function.
Update the system library or reinstall
Automation Builder.
See the drive-specific log generated
by Automation Builder.
64A4 Rating ID fault Rating ID load error. Contact ABB.
64A6 Adaptive program Fault in adaptive program. Check the fault code extension.
64B1 Internal SSW fault A fatal error in the power-up phase of
System Software (SSW).
SSW runs in partial functionality
mode.
64B2 User set fault Loading user parameter set failed. Make sure a valid user parameter set
exists. Reload if uncertain.
64B3 Macro
parameterization error
Macro parameterization failed, eg.
Parameter default
value that cannot be changed has
been attempted to write.
64E1 Kernel overload Operating system error.
Note: This fault cannot be reset.
Reboot the control unit using
parameter 96.08 Control board boot
or by cycling power. If the problem
persists, contact ABB.
6581 Parameter system Parameter load or save failed. Try forcing a save using parameter
96.07 Parameter save manually.
65A1 FBA A parameter
conflict
Requested functionality is not
activated.
Check PLC programming.
Check parameter groups 50 Fieldbus
adapter (FBA) and 51 FBA A settings.
6681 EFB communication
loss (Programmable
fault: 58.14
Communication loss
action)
Communication failed in embedded
fieldbus (EFB) communication.
Check the status of the fieldbus
master (online/offline/error etc.).
Check cable connections to the
EIA-485/X5 terminals 29, 30 and 31
on the control unit.
6591 Backup/Restore
timeout
During backup creating or
restoring operation a panel or PC-
tool has failed to communicate with
the drive as part of this operation.
Check panel or PC-tool
communication and if it is still in
backup or restore state.
6682 EFB configuration file Embedded fieldbus (EFB)
configuration file could not be read.
Reload the firmware or replace the
unit. Contact ABB.
6683 EFB invalid
parameterization
Embedded fieldbus (EFB) parameter
settings inconsistent or not
compatible with selected protocol.
Check parameter group 58
Embedded fieldbus.
Code
(hex)
Fault / Aux. code aux
code visible only on
assistant control panel
and drive composer)
Cause What to do
1 – Starting OS time tick failed 5 – Initializing WoRm volumes failed
2 – Creating system tasks failed 6 – Loading FPGA configuration failed
3 – Initializing file system failed 7 – Loading application program failed
4 – Checking file system failed