162 Parameters
14.48 AI2 min (Visible when 14.01 Module 1 type = FIO-11 or FAIO-01)
Defines the minimum value for analog input AI2.
See also parameter 14.21 AI tune.
0.000 mA or V
-22.000…22.000 mA
or V
Minimum value of AI2. 1000 = 1 mA
or V
14.49 AI2 max (Visible when 14.01 Module 1 type = FIO-11 or FAIO-01)
Defines the maximum value for analog input AI2.
See also parameter 14.21 AI tune.
10.000 mA or
V
-22.000…22.000 mA
or V
Maximum value of AI2. 1000 = 1 mA
or V
14.50 AI2 scaled at AI2 min (Visible when 14.01 Module 1 type = FIO-11 or FAIO-01)
Defines the real value that corresponds to the minimum
analog input AI2 value defined by parameter 14.48 AI2
min.
0.000
-32768.000
…32767.000
Real value corresponding to minimum AI2 value. 1 = 1
14.51 AI2 scaled at AI2 max (Visible when 14.01 Module 1 type = FIO-11 or FAIO-01)
Defines the real value that corresponds to the maximum
analog input AI2 value defined by parameter 14.49 AI2
max. See the drawing at parameter 14.50 AI2 scaled at
AI2 min.
100.000
-32768.000
…32767.000
Real value corresponding to maximum AI2 value. 1 = 1
14.56 AI3 actual value (Visible when 14.01 Module 1 type = FIO-11)
Displays the value of analog input AI3 in mA or V
(depending on whether the input is set to current or
voltage).
This parameter is read-only.
-
-22.000…22.000 mA
or V
Value of analog input AI3. 1000 = 1 mA
or V
14.57 AI3 scaled value (Visible when 14.01 Module 1 type = FIO-11)
Displays the value of analog input AI3 after scaling. See
parameter 14.65 AI3 scaled at AI3 min.
This parameter is read-only.
-
-32768.000
…32767.000
Scaled value of analog input AI3. 1 = 1