EasyManua.ls Logo

ABB COMMANDER 351 - Page 25

ABB COMMANDER 351
104 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
23
1.xx
1
COdE
1.xx
OFF
AtNE
1..xx
xxxx
xxxx
xxxx
xxxx
2.8.3 Auto-tune
Accessing the Auto-tune Facility
From any operating frame, press and hold the key until the
'COdE' frame is displayed.
Set the correct auto-tune password.
Auto-tune Enable
Select the type of auto-tune required.
Single Loop Templates
OFF Off
A Type A
b Type B
Auto-tune is started automatically when the key is pressed.
Auto-tune can be stopped at any time by pressing the key.
Note. P + I control only – set the derivative term to 'OFF'
in the Tuning Level – see Section 3.2.
Return to the Operating Level.
2 OPERATOR LEVEL
Set Point
PV
1
4
=
Type A
1
/
4
wave damping
Type B Minimum Overshoot
Set Point
PV
x
1
x
2
x
1
x
2
Fig. 2.8 Autotune Types

Table of Contents