2 OPERATOR LEVEL
Note 1. The time taken to complete auto-tune depends upon the system response time.
Note 2. Time Proportioning – the cycle time must be set prior to running an auto-tune. The
cycle time is not changed by the auto-tune.
2.8.2 'At Set Point' Auto-tune
If the process variable is within 10% of the set point, 'at set point' tuning is carried out.
'At set point' tuning – manipulates the control output to produce a controlled oscillation of the
process.
A step change of ±10% of the starting output value is applied initially. This is adjusted to give an
amplitude of oscillation 3 times the noise level.
Once the amplitude and period of oscillation are consistent (minimum 2 cycles, maximum 4
cycles) PID parameters are calculated.
If no errors exist the controller enters auto mode and begins to control the process using the new
PID parameters.
If an error occurs during the auto-tune, the controller reverts to manual mode with the control
output set to the default output value. An error message is displayed in the operator level –
see Table 2.1.
t
SPT
PV
Auto-tune
complete
Controlling to
Set Point
B Process response during auto-tune
+2%
– 2%
t
PV
A Stable process before auto-tune
SPT
< ±10 span
12 hours max.
Fig 2.7b Typical At Set Point Auto-tune Cycles