ABB COMMANDER 351 - Level 3 - Set Points

ABB COMMANDER 351
104 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
32
8
SEtP
LEV.3
3.00
1.000
rAtO
0
BIAS
3.06
3.07
400
LSP4
3.04
200
LSP2
3.02
500
LSP1
3.01
•1
•2
•2
•1
3.00...3.07
3 SET UP MODE
•1 Displayed only if a local set point source is selected – see Section 4.5/ Set Point Configuration/
Local/Remote Set Point Source.
•2 Displayed only for templates with a remote set point.
3.3 Level 3 Set Points
Note. Level 3 is not applicable if Auto/Manual Station or Indicator templates are selected.
Level 3 Set Points
Note. To select this frame from anywhere in this page,
press and hold the key for a few seconds.
Local Set Point Value 1
Set the default local set point value.
[Within set point high and low limits, in engineering units – see
Level 9]
Local Set Point Values 2 to 4
[Within set point high and low limits, in engineering units – see
Level 9]
Remote Set Point Ratio
The remote set point value is
(ratio x remote set point input) + bias.
[0.001 to 9.999]
Remote Set Point Bias
[In engineering units]
Continued…