4 CONFIGURATION MODE
4.10 Level E Calibration
Analog Input 3 Offset Calibration
Analog Input 3 Value in Engineering Units
Offset [In engineering Units]
If the
and keys are not operated for three seconds the display
reverts to the offset value only.
Analog Input 3 Span Calibration
Analog Input 3 Value in Engineering Units
Span Adjustment
[0.750 to 1.250]
If the
and keys are not operated for three seconds the display
reverts to the offset value only.
Position Feedback Calibration
Select the calibration required.
NO No Calibration
AUtO Auto Calibration
_AN Manual Calibration
Regulator Travel Time
[0 to 5000 seconds]
Ensure that the value entered is compatible with the regulator motor, as
this is used to determine the length of travel of the feedback mechanism.
Motorized Valve Feedback Fully-closed Position
NO No action
YES Fully closes the valve automatically and sets the electrical
input to low range value.
Note. Input value flashes when calibration is in progress.
Motorized Valve Feedback Fully-open Position
NO No action
YES Fully opens the valve automatically and sets the electrical input
to high range value.
Note. Input value flashes when calibration is in progress.
Continued in Cold Junction Reference Value frame.
•1 Displayed only if Motorized Valve with feedback output type is selected – see Section 4.2, Basic Configuration.