ControlMaster CM30, CM50 and CMF310
Universal process controllers,
1
/4,
1
/2 DIN and fieldmount Appendix B – Error Codes
IM/CM/ED–EN Rev. X 107
B.2 Profile Error Codes
99 Analog Input State C2 (I/P 4– CM30)
100 Setpoint Remote Mode State 1
101 Setpoint LSPT 1 Selected State 1
102 Setpoint LSPT 2 Selected State 1
103 Setpoint LSPT 3 Selected State 1
104 Setpoint LSPT 4 Selected State 1
105 Setpoint Remote Mode State 2
106 Setpoint LSPT 1 Selected State 2
107 Setpoint LSPT 2 Selected State 2
108 Setpoint LSPT 3 Selected State 2
109 Setpoint LSPT 4 Selected State 2
110 Digital Input State 1
111 Digital Input State 2
112 Digital Input State 3
113 Digital Input State 4
114 Digital Input State 5
115 Digital Input State 6
123 Totalizer Run State 1
124 Totalizer Wrap Pulse 1
125 Totalizer Intermediate Pulse 1
126 Totalizer Run State 2
127 Totalizer Wrap Pulse 2
128 Totalizer Intermediate Pulse 2
131 Logic Equation Result 1
132 Logic Equation Result 2
133 Logic Equation Result 3
134 Logic Equation Result 4
135 Logic Equation Result 5
136 Logic Equation Result 6
137 Logic Equation Result 7
138 Logic Equation Result 8
139 Real Time Alarm State 1
140 Real Time Alarm State 2
141 Alarm State 1
142 Alarm Ack State 1
143 Alarm State 2
144 Alarm Ack State 2
145 Alarm State 3
146 Alarm Ack State 3
147 Alarm State 4
148 Alarm Ack State 4
149 Alarm State 5
150 Alarm Ack State 5
151 Alarm State 6
152 Alarm Ack State 6
153 Alarm State 7
154 Alarm Ack State 7
155 Alarm State 8
156 Alarm Ack State 8
157 Time Prop State 1
Error Code Error Description
158 Time Prop State 2
159 Time Prop State 3
160 Time Prop State 4
161 Control O/P Auto State 1
162 Control O/P Manual State 1
163 Control O/P Track Status 1
164 Control O/P Auto State 2
165 Control O/P Manual State 2
166 Control O/P Track Status 2
167 Analog O/P Loop break A1
168 Analog O/P Loop break B1
169 Mot Valve Close Relay State 1
170 Mot Valve Open Relay State 1
171 Mot Valve Sticking State 1
172 Mot Valve Tri State 1
173 Mot Valve Tri State 2
174 Mot Valve Close Relay State 2
175 Mot Valve Open Relay State 2
176 Mot Valve Sticking State 2
177 Delay Timer State 1
178 Delay Timer State 2
189 Toggle Signal
190 Edge Signal
Error Code Error Description
1 Jump Target Invalid
Current active program is configured to jump
to another program, upon the completion of this
action it is found that the next program has
been configured incorrectly.
2 Retort Rampback Invalid
Retort Rampback value is a negative number
and must be changed.
3 Retort Previous Invalid
There is no previous segment therefore the
program is unable to jump back to the last ramp
rate.
4 PV Invalid
The Process Variable has failed.
5 Local Setpoint has Failed
The Local setpoint has become invalid. This
may be that it has travelled outside of its
permissible limits.
9 Validation
The current program is configured incorrectly
and therefore judged invalid by the software
validation.
Error Code Error Description