ControlMaster CM30, CM50 and CMF310
Universal process controllers,
1
/4,
1
/2 DIN and fieldmount 7 Advanced Level
44 IM/CM/ED–EN Rev. X
…Input/Output
Analog Outputs The analog outputs can be configured to retransmit any analog value and have a
configurable range from 0 to 24 mA. Output 1 can also be configured to function as a
digital output.
Analog Output 1 (4) Note. CM30 / 50: Analog Output 2 available only if an option board is fitted –
see pages 16 (CM30) and 17 (CM50) for option board details.
CMF310: Analog Outputs 3 / 4 available only if an optional Output / Slope
Relays board is fitted – see page 20.
Output Type Selects the output type required (applicable only to Analog Output 1).
Source Selects the parameter to be assigned to the output – see Appendix A, page 104 for
description of sources.
Elect. Low* The current output required when the source value is equal to the Eng Low value –
see page 43.
Elect. High* The current output required when the source value is equal to the Eng High value –
see page 43.
Auto Eng Range* If enabled (On) the Eng High and Eng Low values for the output are set automatically
to the engineering range values of the source.
Eng Low* The minimum engineering range output value.
Eng High* The maximum engineering range output value.
Polarity** Sets the polarity of the output signal.
If set to Negative, the output is energized when source is inactive.
If set to Positive, the output is energized when source is active.
*Not applicable if Output Type is Digital or Source is None.
**Not applicable if Output Type is Analog or Source is None.