EasyManua.ls Logo

ABB EQmatic - Mounting and Installation

ABB EQmatic
107 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ABB EQmatic
Device technology
QA/S x.yy.1 | 2CDC512090D0202 17
2.3 Mounting and installation
The device is a modular DIN rail component for quick installation in distribution boards on 35 mm mounting
rails according to DIN EN 60 715.
The mounting position can be selected as required.
The electrical connection is made using screw terminals. The device connects to the bus via the screw
terminal. The terminal assignment is given on the housing.
The device is ready for operation once the main voltage is applied and the initialization process has
finished (green LED continuously illuminated).
The device must be accessible for operation, testing, visual inspection, maintenance and repair in
compliance with DIN VDE 0100-520.
Prerequisites for commissioning
A Windows PC or laptop with a web browser (Internet Explorer, Firefox or Chrome recommended) and an
Ethernet connection are required to commission the device.
Mounting and commissioning are only allowed to be carried out by electricians. The standards, directives,
regulations and specifications applicable in the related country must be observed during the planning and
setting up of electrical installations and security systems for intrusion and fire detection.
Protect the device against damp, dirt and damage during transport, storage and operation!
Only operate the device within the specified technical data!
The device should only be operated in an enclosed housing (distribution board)!
Disconnect the device from the supply of electrical power before mounting.
Danger
To avoid dangerous touch voltages which originate through feedback from different phase conductors,
all poles must be disconnected on extending or modifying the electrical connections.
Supplied state
IP address assignment is set to automatic addressing (DHCP/AutoIP) in the factory.
Language English
Currency EUR
Cleaning
Disconnect the device from the supply of electrical power before cleaning. If devices become dirty, they
can be cleaned using a dry cloth or a cloth dampened with a soapy solution. Corrosive agents or solutions
must never be used.
Maintenance
The device is maintenance-free. In the event of damage, e.g. during transport and/or storage, repairs are
not allowed to be made.