EasyManua.ls Logo

ABB ETL600 - Page 355

ABB ETL600
382 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Revision: Language: Page:
ETL600 Commissioning Report
EN C7/C10
HE
Test
No.
Test procedure
Test point
Permissible
value
Units
Test
result
C.11.5 Pax 4-wire
Mark if configured:
N11
[ ]
N22
[ ]
N54
[ ]
Test E-Wire:
Close and open at
Remote equ. at terminal,
telephony 4a-4b
Terminal, telephony
3a-3b
E-Wire must toggle
N11
[ ]
N22
[ ]
N54
[ ]
Measure Output level.
Feed 800 Hz with
configured input level of
remote PAX (Default:
-3.5 dBm).
(Activate at terminal,
telephony 4a-4b)
Feed into rem. equ. at
terminal, telephony
1a-1b
Measure at terminal,
telephony 2a-2b
Configured Output
level ±1 dB
(Def.: -3.5 dBm)
dBm
(600 )
N11: ___________
N22: ___________
N54: ___________
PAX-BLOCKING normal
Measure at terminal,
telephony 6a-6b,
6b-7a
6a-6b is open
6b-7a is closed
N11
[ ]
N22
[ ]
N54
[ ]
PAX-BLOCKING
blocked
Interrupt local loop, wait
about 30 sec.
Measure at terminal,
telephony 6a-6b,
6b-7a
6a-6b is closed
6b-7a is open
N11
[ ]
N22
[ ]
N54
[ ]
C.11.6 Pax 4/2-wire
Mark if configured:
N11
[ ]
N22
[ ]
N54
[ ]
Test E-Wire:
Close and open at
terminal, telephony
4a-4b
Terminal, telephony
3a-3b
E-Wire must toggle
N11
[ ]
N22
[ ]
N54
[ ]
Measure Output level at
AF1.
Feed 800 Hz with
configured input level
(Def.: -3.5 dBm).
(Activate at terminal,
telephony 4a-4b)
Feed into terminal,
telephony 1a-1b
Measure at terminal,
telephony 2a-2b
Configured Output
level ±1 dB
(Def.: -3.5 dBm)
dBm
(600 )
N11: ___________
N22: ___________
N54: ___________
Measure Output level at
PAX2W.
Feed 800 Hz with
configured input level
(Def.: -3.5 dBm).
(Activate at terminal,
telephony 4a-4b)
Feed into terminal,
telephony 1a-1b
Measure at terminal,
telephony 8a-8b
Configured Output
level ±1 dB
(Def.: -7.0 dBm)
dBm
(600 )
N11: ___________
N22: ___________
N54: ___________
Test Local/Transit:
Measure Output level at
AF1.
Feed 800 Hz with
configured input level of
PAX2W (Def: -0.0 dBm).
Activate terminal,
telephony 5a-4b and
4a-4b.
Feed into rem. equ. at
terminal, telephony
8a-8b
Measure at terminal,
telephony 8a-8b
Configured Output
level ±1.5 dB
(Def.: -7.0 dBm)
dBm
(600 )
N11: ___________
N22: ___________
N54: ___________
© ABB Switzerland Ltd Form 1KHw001495-EN
Rev. A

Table of Contents

Related product manuals