Revision: Language: Page:
ETL600 Commissioning Report
EN C8/C10
HE
Test
No.
Test procedure
Test point
Permissible
value
Units
Test
result
PAX-BLOCKING normal
Measure at terminal,
telephony 6a-6b,
6b-7a
6a-6b is open
6b-7a is closed
N11
[ ]
N22
[ ]
N54
[ ]
PAX-BLOCKING
blocked
Interrupt local loop, wait
about 30 sec.
Measure at terminal,
telephony 6a-6b,
6b-7a
6a-6b is closed
6b-7a is open
N11
[ ]
N22
[ ]
N54
[ ]
C.11.7 Transit mode for
E&M wire
Mark if configured:
N11
[ ]
N22
[ ]
N54
[ ]
Test E-Wire:
Close and open at
Remote equ. at terminal,
telephony 4a-4b
Terminal, telephony
3a-3b
E-Wire must toggle
N11
[ ]
N22
[ ]
N54
[ ]
C.11.8 Testing the
teleoperation ports
N11 N22 N34 N54 N65
C.11.9 Teleoperation AF1, if
not used for telephony
Mark if configured:
[ ] [ ] [ ] [ ] [ ]
Fed input level, [dBm],
@ 800 Hz at AF1-IN
Expected Output
level at AF1-OUT
Measured Output level
at AF1-OUT
N11: ___________±1
N22: ___________±1
N34: ___________±1
N54: ___________±1
N65: ___________±1
Feed into terminal,
telephony 1a-1b
Measure at terminal,
telephony 2a-2b
Ext. Boost not active.
N11: _______±1
N22: _______±1
N34: _______±1
N54: _______±1
N65: _______±1
dBm
(600 Ω)
N11: ___________
N22: ___________
N34: ___________
N54: ___________
N65: ___________
N11 N22 N34 N54 N65
C.11.10 Teleoperation AF2
Mark if configured:
[ ] [ ] [ ] [ ] [ ]
Fed input level, [dBm],
@ 800 Hz at AF2-IN of
remote.
Expected Output
level at AF2-OUT
Measured Output level
at AF2-OUT
N11: ___________±1
N22: ___________±1
N34: ___________±1
N54: ___________±1
N65: ___________±1
Feed into terminal,
teleop. 3a-3b
Measure at terminal,
teleop. 4a-4b
ext. Boost not active.
N11: _______±1
N22: _______±1
N34: _______±1
N54: _______±1
N65: _______±1
dBm
(600 Ω)
N11: ___________
N22: ___________
N34: ___________
N54: ___________
N65: ___________
© ABB Switzerland Ltd Form 1KHw001495-EN
Rev. A