Revision: Language: Page:
ETL600 Commissioning Report
EN C9/C10
HE
Test
No.
Test procedure
Test point
Permissible
value
Units
Test
result
N11 N22 N34 N54 N65
C.11.11 Teleoperation AF3
Mark if configured:
[ ] [ ] [ ] [ ] [ ]
Fed input level, [dBm],
@ 800 Hz at AF3-IN of
remote.
Expected Output
level at AF3-OUT
Measured Output level
at AF3-OUT
N11: ___________±1
N22: ___________±1
N34: ___________±1
N54: ___________±1
N65: ___________±1
Feed into terminal,
teleop. 5a-5b
Measure at terminal,
teleop. 6a-6b
ext. Boost not active.
N11: _______±1
N22: _______±1
N34: _______±1
N54: _______±1
N65: _______±1
dBm
(600 )
N11: ___________
N22: ___________
N34: ___________
N54: ___________
N65: ___________
N11 N22 N34 N54 N65
C.11.12 Teleoperation AF4
Mark if configured:
[ ] [ ] [ ] [ ] [ ]
Fed input level, [dBm],
@ 800 Hz at AF4-IN of
remote.
Expected Output
level at AF4-OUT
Measured Output level
at AF4-OUT
N11: ___________±1
N22: ___________±1
N34: ___________±1
N54: ___________±1
N65: ___________±1
Feed into terminal,
teleop. 7a-7b
Measure at terminal,
teleop. 8a-8b
ext. Boost not active.
N11: _______±1
N22: _______±1
N34: _______±1
N54: _______±1
N65: _______±1
dBm
(600 )
N11: ___________
N22: ___________
N34: ___________
N54: ___________
N65: ___________
N11 N22 N54
C.11.12 Teleoperation AF4
used for ext.
teleprotection
Mark if configured:
[ ]
[ ] [ ]
Test EXT-BOOST:
Activate at remote
equ. at terminal,
teleop. 9a-9b.
Fed input level, [dBm],
@ 800 Hz at AF4-IN
Feed into rem. equ. at
terminal, teleop.7a-7b
Expected Output
level at AF4-OUT
Measured Output level
at AF4-OUT
N11: ___________
N22: ___________
N54: ___________
Measure at terminal,
teleop. 8a-8b
N11: _______±1
N22: _______±1
N54: _______±1
dBm
(600 )
N11: ___________
N22: ___________
N54: ___________
C.12 V.11 ports
C.12.1 V.11 Port 1
Front plate P4LT/P4LU
BER test
V.11 PORT 1
BER 10
-5
during ____ sec
[ ]
C.12.2 V.11 Port 2
Front plate P4LT/P4LU
BER test
V.11 PORT 2
BER 10
-5
during ____ sec
[ ]
© ABB Switzerland Ltd Form 1KHw001495-EN