Note/IllustrationAction
ELECTROSTATIC DISCHARGE
(ESD)
The unit is sensitive to ESD. Before
handling the unit read the safety inform-
ation in section The unit is sensitive to
ESD on page 45.
2
xx2300001836
Hook up the Connected Services gate-
way to the bracket and push carefully into
position.
3
Reconnect any connectors disconnected
at removal.
4
Reconnecting the antenna
Note/IllustrationAction
Note
The operating conditions must be such that
there is a minimum separation distance of
20 cm between the dedicated antenna and
nearby persons.
Place the magnet part of the antenna on
the outside of the cabinet.
1
Note
The Connected Services antenna is installed
by the customer, and the cable routing can
therefore differ.
Follow the cable routing recorded during
the disassembly when you reconnect the
antenna cable.
2
Continues on next page
214 Product manual - OmniCore V400XT
3HAC081697-001 Revision: A
© Copyright 2022-2023 ABB. All rights reserved.
5 Repair
5.2.4 Replacing the 3G Connected Services gateway
Continued