Note/IllustrationAction
Location of wrist strap button:
ELECTROSTATIC DISCHARGE
(ESD)
The unit is sensitive to ESD. Before
handling the unit read the safety inform-
ation in section The unit is sensitive to
ESD on page 45.
3
xx2300001842
Removing the HMI signal connector
Note/IllustrationAction
Cut the cable ties and remove the cables
out from the clips in the cabinet carefully.
Note
Make records about the sequence that
cables are removed. The cables need to
be installed in the same position.
1
Disconnect all connectors from the unit
to be replaced.
2
Continues on next page
296 Product manual - OmniCore V400XT
3HAC081697-001 Revision: A
© Copyright 2022-2023 ABB. All rights reserved.
5 Repair
5.3.3 Replacing the HMI signal (FlexPendant) connector