FEM630 | ELECTROMAGNETIC FLOWMETER | OI/FEM630-EN REV. A
9 ...Diagnosis / error messages
...Overview
Error no. / Range Error text Current output Digital output Pulse output LCD display Error maskable?

Inhouse temp. alarm.
Reduce ambient
temperature.
Current value - no
change.
No Answer
No Answer
Current value -
no change.

EPD alarm.
Secure pipe is
completely filled.
Alarm - configured as in
menu ‘Curr. at EPD
Alarm’.
Alarm, if DO as ‘Logic /
Alarm Signal / EPD
Alarm’ is configured
 
Menu ‘...Group
Masking’.

TFE alarm.
Secure pipe is
completely filled.
Alarm - configured as in
menu ‘Curr. at TFE
Alarm’.
Alarm, if DO as ‘Logic /
Alarm Signal / TFE
Alarm’ is configured
Current value - no
change.
Current value -
no change.
Menu ‘...Group
Masking’.

Sensor temp. limits
alarm.
Change limits or
change fluid
temperature.
Current value - no
change.
No Answer
Current value - no
change.
Current value -
no change.
Menu ‘...Group
Masking’.

Conductivity limits
alarm.
Change limits or
Check application.
Current value - no
change.
Alarm, if DO as ‘Logic /
Alarm Signal /
Conductivity’ is
configured
Current value - no
change.
Current value -
no change.
Menu ‘...Group
Masking’.

Gas bubble alarm.
Check conditions of
application.
Current value - no
change.
Alarm, if DO as ‘Logic /
Alarm Signal / Gas
bubble Alarm’ is
configured
Current value - no
change.
Current value -
no change.
Menu ‘...Group
Masking’.


saturated.
CO process value out
of range. Adapt
Qmax.
Alarm - configured as in
menu ‘„Curr.Out >

Current value - no
change.
Current value - no
change.
Current value -
no change.
Menu ‘...Group
Masking’.



CO process value out
of range. Adapt
Qmax.

electronics

error.
Defective Card.

Service.
Does not react anymore Current value - no
change.
Current value - no
change.
Current value -
no change.
Menu ‘...Group
Masking’.

electronics

error.
Defective Card.

Service.
Does not react anymore Current value - no
change.
Current value - no
change.
Current value -
no change.
Menu ‘...Group
Masking’.