FEM630 | ELECTROMAGNETIC FLOWMETER | OI/FEM630-EN REV. A
Menu / parameter Description
Input/Output
.
.
.
.
.
.
.
.
.
Output Value
Selection of process variable issued at the corresponding current output.
•
•
•
Curr.Out Mode
• Select the operating mode for the current output.
• ‘4-20mA FWD’ Output flow rate in forward flow:
4 mA = no flow
20 mA = maximum flow
• ‘4-12-20 mA’: Output flow rate in forward and reverse flow:
4 mA = maximum flow in reverse flow
12 mA = no flow
20 mA = maximum flow in forward flow
• ‘4-20mA FWD/REV’: Output flow rate in forward and reverse flow without distinction of flow direction:
4 mA = no flow
20 mA = maximum flow
Curr.Out at Alarm
Selection of status of the current output in error condition.
The output ‘low' or ‘high’ current is set in the subsequent menu.
Default setting: High Alarm.
Low Alarm Sets the current for Low Alarm.
High Alarm Sets the current for High Alarm.
• Hold Last Value: The last measured value is retained and issued.
• High Alarm: The high alarm current is issued.
• Low Alarm: The low alarm current is issued.
Default setting: Hold Last Value.
8 ...Operation
...Parameter descriptions
Menu: Input/output