FEP630, FEH630 ELECTROMAGNETIC FLOWMETER | OI/FEP630/FEH630-EN REV. D 115
Error no. / Range Error text Current output Digital output Pulse output LCD display Error maskable?
F090.035 /
Electronics
ADC RX210 com. error.
Call service.
0 Hz 0 % No
F088.012 /
electronics
FEB communication error.
EMC disturbance. Call Service.
0 Hz 0 % No
F086.018 /
Electronics
Curr.Out 31 / 32 com error.
Defective Board. EMC
disturbance. Call Service.
Current value - no
change.
Current value - no
change.
No
F084.010 /
electronics
NV data defect.
Data storage irreparable. Call
Service.
0 Hz 0 % No
F082.013 /
Electronics
Incompatible Frontend Board.
Frontend not fit to
Motherboard. Call Service.
0 Hz 0 % No
F081.025 /
electronics
MB voltages outside range.
Defective Motherboard HW.
Call Service.
0 Hz 0 % No
C078.003 / Config. Flowrate to zero.
Check digital in terminals.
4 mA (0 % flow) Current value - no
change.
0 Hz 0 % Menu ‘...Group
Masking’.
C076.005 / Config. All totalizer stopp.
Check digital in terminals.
Current value - no
change.
Current value - no
change.
Current value - no
change.
Current value - no
change.
C074.006 / Config. Totalizer reset.
Reset of one or more
Totalizers.
Current value - no
change.
Current value - no
change.
Current value - no
change.
Current value - no
change.
Menu ‘...Group
Masking’.
C072.002 / Config. Simulation is on.
Simulated values.
Switch off Simulation Mode.
Current value - no
change.
Current value - no
change.
Current value - no
change.
Current value - no
change.
C070.026 / Config. An alarm is simulated.
Switch off alarm simulation.
Current value - no
change.
Current value - no
change.
Current value - no
change.
Current value - no
change.